How do dry bulb, wet bulb, and black globe thermometers differ?

Dry bulb measures shaded air temperature alone (e.g., 32°C / 90°F), wet bulb measures evaporative cooling from air temperature plus humidity (e.g., 26°C / 79°F), and a 150 mm black globe measures radiant solar and surface heat balanced against wind (e.g., 52°C / 126°F in full sun).

The three thermometers, and what each one is sensitive to.
ThermometerSetupSensitive toOn a hot sunny day (°C)
Dry bulbShaded, ventilated, dryAir temperature only32°C
Wet bulbShaded, ventilated, wet wickAir temperature and humidity26°C
Black globeCentre of a 150 mm matt black sphere, in the openRadiant heat, plus wind52°C

Those example figures are what this site's WBGT estimator produces at 32°C, 60% humidity, light wind and a high summer sun. The spread is the point: a single "temperature" cannot describe a situation in which one instrument reads 26 and another reads 52.

How do dry bulb, wet bulb, and globe temperatures combine in WBGT?

Dry bulb and wet bulb together determine relative humidity (with zero difference at 100% RH), while the black globe independently captures radiant heat—which is why outdoor WBGT combines all three as 0.7 natural wet bulb + 0.2 globe + 0.1 dry bulb. The wet bulb and dry bulb together determine the humidity — that is what a psychrometer does, and it is why two thermometers were enough to measure humidity for two centuries.

The globe is independent. It responds to radiation, which the other two are shielded from by design. That is exactly why WBGT needs all three: humidity from the first pair, radiant load from the third.

Worked example: the same air, in sun and in shade

Dry bulb
32°C in both cases — the air is the air
Wet bulb, shaded
26°C in both cases
Black globe, in sun
52°C
Black globe, in shade
Close to 32°C
4°C The difference the globe makes to WBGT between sun and shade, from a weighting of only 0.2. Which is why standards use WBGT and not the heat index.

Why do HVAC psychrometric charts use dry bulb and wet bulb differently?

HVAC engineers pair shaded dry-bulb and aspirated wet-bulb temperatures on psychrometric charts to calculate air enthalpy and cooling-coil loads in kW or tons, whereas occupational heat-stress standards add a black globe thermometer to measure radiant heat on the human body. Search for "dry bulb temperature" and much of what comes back is HVAC engineering: psychrometric charts, enthalpy, sensible and latent loads, coil sizing. That field uses the same two thermometers for a completely different purpose — designing equipment rather than protecting people — and its calculators convert between dry bulb, wet bulb and relative humidity as an end in itself.

This site does not cover that, for a simple reason: a calculator whose output is relative humidity is a humidity tool, not a heat-stress tool, and mixing the two would produce pages that answer neither question well.

What is here:

What mistakes do people make when reading ISO 7243 WBGT formulas?

The two most common ISO 7243 mistakes are substituting shaded psychrometric wet bulb for unshielded natural wet bulb (which reads higher in sun) and applying the indoor shade formula (0.7 Tw + 0.3 Tg) to sunlit outdoor work instead of the outdoor formula (0.7 Tw + 0.2 Tg + 0.1 Td). Two traps:

  1. "Wet bulb" in a WBGT context means the natural wet bulb — out in the open, exposed to sun and ambient wind — not the shaded, ventilated psychrometric one. It reads higher. This is the single most common misreading of ISO 7243.
  2. The weights change indoors. Outdoors WBGT is 0.7 natural wet bulb + 0.2 globe + 0.1 dry bulb. Indoors or in full shade it is 0.7 natural wet bulb + 0.3 globe, with no dry bulb term at all.